MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany
Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt-group.com
23 / 67
Technical Manual
Motion Detector/Automatic Switch 55/63 [SCN-BWM55/63(T)(06).x2]
State 07/2025 - Version 1.4
With the parameter “Fallback of forced guidance/lock (General settings), it is possible to set individually
foreachchannelwhetheritshouldreacttothecongurationfor“Fallbackofforcedguidance/lock”inthe
“General settings”.
The following table shows the associated communication objects:
No. Name/Object function Length Usage
8 Light channel 1 - Input – Lock object 1 Bit Locking the light channel.
8 Light channel 1 - Input – Forced guidance 2 Bit Activate/deactivate forced guidance.
9 Light channel 1 - Input – Lock object ON 1 Bit Switch on the light channel and locking the
light channel in the ON state.
+15 Light channel 2 ...
68 HVAC - Input – Lock object 1 Bit Locking the HVAC channel.
68 HVAC - Input – Forced guidance 2 Bit Activate/deactivate forced guidance.
69 HVAC - Input – Lock object ON 1 Bit Switch on the HVAC channel and locking
the light channel in the ON state.
Table 19: Communication objects – Forced guidance / Lock objects
4.2.1.4 Output objects
Light channel
HVAC channel
The following table shows the available settings:
ETS Text
Dynamic range
[Default value]
Comment
Object type for output – Light Switch
Dimming absolute
Scene
Selection of the object type that is sent
when a motion is detected.
Object type for output – HVAC
Output 2
(Additional switch object)
not active
ON and OFF
Activation of an additional switch object.
Only available for “Light channels”.
Table 20: Settings – Output objects
Object type for output
Theparameterdenesthedatapointtypeoftheoutputobject.
Output 2 (Additional switch object)
In addition, a separate switch object can be activated - regardless of the object type. This is always a 1 Bit
object. If, for example, a dimming value is sent as output object 1, a 1 Bit telegram can also be sent via
output 2 to control a status LED or similar.
Note: This object is only available for light channels!