Technical Manual – Push Button Smart 55/63
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
80
80
4.9 Temperature Setting
Function only available for BE-TASxxT4.01
4.9.1 Temperature- and Humidity measurement
4.9.1.1 Temperature measurement
The following figure shows the menu for temperature measurement:
Figure 46: Settings – Temperature measurement
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Send measured value on
change
▪ not active
▪ active
Setting whether the measured value
should be sent on change
Send measured value
on change of
0,1 … 2 K
[0,1 K]
Setting at which change the
measured value should be sent.
Only visible if "Send measured
value on change" is activated
Send measurement value
cyclic
not send, 1 min – 60 min
[5 min]
Cyclic sending of the measured value
Messages
▪ not active
▪ active
Activation of the message function
Upper message value
20 … 45 °C
[28 °C]
Setting range of the upper/lower
message value.
Only visible when parameter
"Messages" is activated
Lower message value
3 … 30 °C
[18 °C]
Calibration value for
internal sensor
-5 … 5 K
[0 K]
Adjustment for internal sensor
Sensor internal/external
▪ 100% internal
▪ 90% internal/ 10% external
▪ 80% internal/ 20% external
▪ …
▪ 100% external
Setting the weighting between
internal and external sensor
Table 76: Settings – Temperature measurement