MDT BE-TAS55T4.01 handleiding
Handleiding
Je bekijkt pagina 16 van 89

Technical Manual – Push Button Smart 55/63
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
16
16
4 Reference-ETS-Parameter
4.1 General Settings
The following picture shows the menu for the general settings:
Figure 3: General Settings
The following table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Startup time
2 – 240 s
[2 s]
Sets the time between restart
and functional start-up of the
device
Send „Operation“ cyclically
not active
1 min – 4 h
Setting whether a cyclic in-
operation telegram is to be sent
Value for Day/Night
▪ Day = 1 / Night = 0
▪ Night = 1 / Day = 0
Sets the polarity for day / night
switching
Behavior after bus power return
Values for toggle
▪ no request
▪ request
Setting whether the
values/objects should be
requested automatically on bus
voltage return.
Day/Night object
▪ no request
▪ request
Time/Date
▪ no request
▪ request
Language
▪ German
▪ English
Setting the language.
(see description next page)
Table 7: General Settings