MDT BE-TAS55T4.01 handleiding
Handleiding
Je bekijkt pagina 14 van 89

Technical Manual – Push Button Smart 55/63
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
14
14
Standard Settings – Logic function
No.
Name
Object Function
Length
C
R
W
T
U
40
Logic 1k
Input 1 A
1 Bit
X
X
X
X
41
Logic 1
Input 1 B
1 Bit
X
X
X
X
42
Logic 1
Output 1
Output 1 Scene
Output 1 Value
Output 1 Value
1 Bit
1 Byte
2 Bit
1 Byte
X
X
X
+ 3
next Logic
Table 4: Communication objects – Logic Function
Standard Settings – Temperature and Air Humidity Measurement
No.
Name
Object Function
Length
C
R
W
T
U
80
Temperature
Send measured value
2 Byte
X
X
X
81
Temperature
External sensor
2 Byte
X
X
82
Temperature
Max. value exceeded
1 Bit
X
X
X
83
Temperature
Min. value fallen below
1 Bit
X
X
X
84
Relative air humidity
Send measured value
2 Byte
X
X
X
85
Relative air humidity
External humidity sensor
2 Byte
X
X
X
X
86
Relative air humidity
Max. value exceeded
1 Bit
X
X
X
87
Relative air humidity
Min. value fallen below
1 Bit
X
X
X
88
Dew point temperature
Send measured value
2 Byte
X
X
X
89
Dew point temperature
Comparison value
2 Byte
X
X
90
Dew point temperature
Send alarm
1 Bit
X
X
X
Table 5: Communication objects – Temperature and Air Humidity Measurement