Legrand Ensto Pro EVF200 handleiding

40 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 17 van 40
RAK112B_ENG / 2023-06-27
17 / 40
Figure 4
Put the adapter element on the foundation.
Attach the adapter element to the foundation attachment
bar with bolts 3 pcs (included).
Remove the upper nuts and upper pair of washers from the
adapter element. (Make sure that there is one polyamide
washer on each side of the mounting box.)
Pull the supply cable and the possible data cable through
the hole in the center of the adapter.
Figure 5
Put the mounting box on the adapter element.
Attach the mounting box in place with the washers and the
nuts you removed from the adapter element. (Make sure
that there is one polyamide washer on each side of the
mounting box.)
Handy hint to adjust the mounting box level: First ip the
mounting box upside down and put the nuts under it so
that the mounting box is horizontal. Then ip the mount-
ing box over again and tighten the upper nuts and wash-
ers.
EVTL32.00: Pull electrical cables through the ground
mounting box cable gland(s) approx. 400 mm measured
from the upper end of the mounting box.
EVTL34.00: Pull electrical cables through the ground
mounting box cable gland(s) and further through the
mounting box cable hole approx. 400 mm measured from
the upper end of the mounting box.
Tighten the cable gland. Close the unused cable entries
with cable gland plugs.
Figure 6
Open the maintenance door of the charging station.
Remove the nuts and washers from the ground mounting
box.
Lift the charging station on the mounting box and pull the
electrical cables through the cable hole.
Attach the charging station in place with the washers and
the nuts you removed from the ground mounting box.
EVTL32.00: Remove the supply cable sheath at the length
of max. 200 mm.
EVTL34.00: Remove the supply cable sheath beginning
from the cable gland exit.
Cut the supply cable conductors to applicable lengths. The
earth conductor must be long enough, so that if a fault oc-
curs it is the last one that comes loose.
Strip the supply cable conductors 25 mm.
Connect the supply cable wires to the supply terminal
blocks.
Make sure that the PE is connected to the charging station.
Switch on F0, F1, F2 (if present) and QF1.
Close the maintenance door.
250
395
Ø15
600
450
Ø115 (x4)
Attach the EVF in correct position with bolts
4
5