Handleiding
Je bekijkt pagina 25 van 25

KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS KWIKOOL
25
NOTE
Users will be notified of incorrect rotation by an audible alarm and
the display showing PH. This will clear automatically when the
phase issue is corrected by exchanging the line voltage wire as
described above in this section.
Supply Air Fan Speed
KWIB & KIB120XX II Iceberg Series Systems are 2-stage systems and have a fan speed for each
stage. This is not user settable. These systems always start on first stage fan speed (low) in COOL
MODE or FAN MODE, second stage fan speed (high) only operates in COOL MODE when the second
stage compressor is running.
CAUTION
Do not tamper with or attempt to adjust the VFD system.
VFD (Variable Frequency Drive)
Only used on KIB120XX II Iceberg Series (10-ton Systems), to optimize the operation of the condenser
fan by slowing down and speeding up the rotations of the blower to maintain the best pressure needed
to operate in the environment. The VFD is located in the left side evaporator access compartment as
seen when facing the control panel. The VFD has a screen that displays the current operating
frequency or any error message needed for fault diagnosis. The VFD is not used on KWIBXX II series
systems nor is it used on smaller KIBXX II Systems. Call Factory Technical support for guidance.
Conditioned Air Supply Drive Belts
The KwiKool KWIB & KIB120XX II Iceberg Series Systems move air over the evaporator coil to remove
heat and moisture from the conditioned space by way of a motor attached to a blower wheel. This
wheel turns by way of a pulley and belt system. Inspect/adjust these belts every 60 days of operation,
replace as needed.
CAUTION
Failure to maintain the drive belts will cause low performance, coil
freezing or in extreme cases damage to the blower/motor in the
event of a belt breaking.
The belts are located inside the right side evaporator access door as seen when facing the control
panel. When adjusting the belts, adjust the tension using the base adjustment screw.
CAUTION
Never adjust the sheave (pulley) as it can cause damage to the
system and/or make the system have poor performance.
Bekijk gratis de handleiding van KwiKool KIB3021-2, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | KwiKool |
| Model | KIB3021-2 |
| Categorie | Airco |
| Taal | Nederlands |
| Grootte | 3684 MB |