KWIKOOL KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS
24
B SPECIAL SECTION FOR KWIB & KIB120XX II SYSTEMS
Compressor Priority Switch
These Iceberg Series Systems have two compressors and two refrigeration circuits that operate
independently of each other and are staged to come on at different intervals as needed for cooling. The
KwiKool Iceberg is equipped with a Compressor Priority Switch located on the top of the control box in
the evaporator access compartment. The rocker switch is factory set to use compressor 1 as the first
stage compressor, or lead compressor, on start up, and compressor 2 as the second stage, or lag
compressor.
The lag compressor comes on when the demand requires it. The rocker switch when moved to the
compressor 2 position reverses the order of the lead and lag compressors. This allows for rotation of
the compressors for even wear. Change this switch position at regular intervals. Factory
recommendation is approximately every 6 months.
CAUTION
Failure to turn off power prior to changing the switch position may
damage the equipment or injure personnel.
Turn off the power to the Iceberg Series System before changing this switch position.
Evaporator Fan Rotation
On KWIB & KIB120XX II Iceberg Series Coolers without the optional factory installed phase monitor,
visually confirm the rotation direction of the Cold Air-Supply fan and correct if needed.
1. When facing the front control panel of the Iceberg Series Cooler, open the right side evaporator
access door with the system in the OFF position.
2. Secure the door from closing and keep clear any objects from the moving or rotating parts.
3. Select FAN mode on the control and turn the system ON briefly and then OFF.
CAUTION
Operating the Iceberg Series Cooler with the Supply air fan
rotating incorrectly will cause low performance and evaporator coil
freezing.
4. The Supply air fan should be rotating in a counter-clockwise direction from this view. If rotating
clockwise, qualified personnel should disconnect power at the source and exchange any incoming
line voltage wire with any other line voltage wire and repeat the previous instructions. KwiKool
Iceberg Series Systems with a factory installed phase monitor will not allow the system to start if the
proper phase is not connected, PH will display and you will hear an audible alarm.