© 2021 KOSTAL Solar Electric GmbH
System monitoring
Inverter settings
Time setting Explanation
Synchronize inverter time Synchronize the time of the inverter with the time of the smartphone.
The following menu items can be used to set the parameters in the inverter, which are specified by the
grid operator. Parameters may only be changed on the inverter by qualified electricians who are familiar
with the system and at the request of the grid operator. Inappropriate settings can be hazardous and
lead to injury or even death of the user or third parties. Material damage to the device and other equip-
ment can also occur.
Grid settings Explanation
Frequency monitoring of level 1
activated
Activate/deactivate frequency monitoring level 1
Grid guideline Select grid guideline (e.g. VDE-AR-N 4105)
Start time Start-up waiting time after switching on the inverter
Start time after grid error Start-up time following inverter grid error
Power gradient Power gradient after switching on the inverter
Power gradient following grid error Power gradient following inverter grid error
Overfrequency limit value Set overfrequency limit threshold value
Underfrequency limit value Set underfrequency protection threshold value
Overvoltage limit value Set overvoltage protection limit value
Undervoltage limit value Set undervoltage protection limit value
Overfrequency switch-o time Set overfrequency switch-o time
Underfrequency switch-o time Set underfrequency shut-o time
Overvoltage switch-o time Set overvoltage switch-o time
Undervoltage switch-o time Set undervoltage switch-o time
Max. grid start voltage
If the supply voltage is higher than the upper limit of the reconnection voltage after
the inverter has been shut down for protection due to a fault, the inverter may not be
reconnected to the grid.
Min. grid start voltage
After the inverter is shut down for protection due to a fault, if the supply voltage is
lower than the lower limit of the reconnection voltage, the inverter may not be recon-
nected to the grid.
Max. grid start frequency
After the inverter is shut down for protection due to a fault, if the grid frequency is
higher than the upper limit of the reconnection frequency, the inverter may not be
reconnected to the grid.
Min. grid start frequency
After the inverter is shut down for protection due to a fault, if the grid frequency is
lower than the lower limit of the reconnection frequency, the inverter may not be
reconnected to the grid.
Mean average voltage limit Set 10 minutes of average overvoltage value