Torque Parameters
Pipe size
Newton meter (N x
m)
Pound-force foot
(lbs-ft)
Kilogram-force
meter (kgs-m)
1/4 (6.35) 15-20 11.1 – 14.8 1.5-2.0
3/8 (9.52) 31-35 22.9-25.8 3.2-3.6
1/2 (12) 45-50 33.2-36.9 4.6-5.1
5/8 (15.88) 60-65 44.3-48.0 6.1-6.6
Dedicated Distribution Device and Wire for Air Conditioner
Min. circuit
ampacity of air
conditioner (A)
Minimum Wire
Cross-sectional
Area (mm2)
Specification of
socket or switch
(A)
Fuse
specification (A)
≤8 0.75 15 15
>8 and ≤10 1.0 15 15
>10 and ≤15 1.5 20 25
>15 and ≤24 2.5 25 40
>24 and ≤28 4.0 35 45
>28 and ≤32 6.0 40 55
Indoor Unit Installation
Step 1: Select Installation Location
Ensure the installation complies with the minimum installation dimensions (defined
below) and meets the minimum and maximum connecting piping length and
maximum change in elevation as defined in the System Requirements section.
Air inlet and outlets must be clear of obstructions, ensuring proper airflow throughout
the room.
Condensation can be easily and safely drained.
All connections to the outdoor unit can be easily made.
Note:
This table is only for reference. The installation must meet the requirements of local
laws and regulations.