Name Reference
Power supply class 2, 230 Vac input, 24 Vac output KIAL-100A
Conguration software with USB cable LCC-S
Accessories
Conguration via LCC-S software (optional)
The software allows to set the alarms, the thresholds, and the time-delay of the instrument.
To access the conguration via software:
- Set the DIP switches as shown beside.
- Connect the cable of the LCC-S to the connection of the transmitter.
Please refer to the user manual of the LCC-S to make the conguration.
The conguration of the parameters can be done either with the DIP switch or via software (you can not
combine both solutions). Switch off the sensor before settings process.
1
2
3
4
Switch actif
1
2
3
4
Active switch
1
2
3
4
Bloque activo
1
2
3
4
Interruttore attivo
Mounting
To mount the transmitter, mount the ABS plate on the wall (drilling: Ø6 mm,
screws and pins are supplied).
Insert the transmitter on the xing plate (see A on the drawing beside). Rotate
the housing in clockwise direction until you hear a “click” which conrms that
the transmitter is correctly installed.
2
Ambient model has not any xing plate.
4 xing holes are inside the back housing. Use them to install the
transmitter on the required location.
Maintenance
Please avoid any aggressive solvent. Please protect the transmitter and its probes from any cleaning product containing formalin, that
may be used for cleaning rooms or ducts.
Precautions for use
Please always use the device in accordance with its intended use and within parameters described in the technical features in order
not to compromise the protection ensured by the device.
Only the accessories supplied with the device must be used.
Setting procedure: “Time 1” for the time-delay 1 is displayed then the time in second. The rst digit blinks, press briey on the
button and scroll the gures. Press on the button more than 3 seconds to validate. Repeat the process until the last digit to set the
time-delay 1 value (from 0 to 600 s) and validate. “Time 2” is displayed the time in second. Repeat the process to set the time-delay 2.
- In falling edge mode, the time-delay 1 corresponds to the time lag before the alarm goes off when the threshold has been reached.
The time-delay 2, corresponds to the time lag before the alarm stops when the measurement is lower than the threshold plus the
hysteresis.
The setting procedure is the same as the rising edge procedure.
- In monitoring mode, the alarm of the transmitter goes off when the measurement is below the lower threshold and higher the high
threshold. The time-delay 1 corresponds to the time lag before the alarm goes off when the measurement is below the lower threshold
and higher the high threshold. The time-delay 2 corresponds to the time lag before the alarm stops when the measurement is between
the lower and higher thresholds.
The setting procedure is the same as the rising edge procedure.
FT – CO2ST_EN – 13/08/19 – Non-contractual document – We reserve the right to modify the characteristics of our products without prior notice.