4.4. Alarms and relays
4.4.1 Alarms
Modbus Register
type
Description Possibilities
Alarm
1
Alarm
2
Alarm
3
Alarm4
4000 4100 4200 4300 Enumeration Alarm mode None
Rising edge
Falling edge
Monitoring
Transmitter state
4010 4110 4210 4310 U8 Channel selection Channel 1
Channel 2
Channel 3
4020 4120 4220 4320 Real Threshold 1 setting According to the connected
probe
4030 4130 4230 4330 Real Threshold 2 setting or hysteresis According to the connected
probe
4040 4140 4240 4340 U16 Delay-time 1 setting From 0 to 600 s
4050 4150 4250 4350 U16 Delay-time 2 setting From 0 to 600 s
4060 4160 4260 4360 U32 Condition (for transmitter state) Ambient temperature too
high
Ambient temperature too low
Memory error
Pressure board error
Probe 1 error
Probe 2 error
Pressure value too high
4080 4180 4280 4380 Boolean Audible alarm 1: activated / 0: deactivated
4090 4190 4290 4390 U8 Acknowledgement duration From 0 to 60 minutes
Description of function and Modbus connections
28