Gas shutoff valve:
A manual gas line shut-off valve must be installed in an easily accessible location. Do not
block access to shut-off valve. The valve is for turning on or shutting off gas to the range.
A Gas Supply Line
B Shutoff Valve "Open" Position
C To Range
GAS PRESSURE REGULATOR
The gas pressure regulator supplied with this range must be used. The inlet pressure to the
regulator should be as follows for proper operation:
Natural gas
LP gas
Minimum pressure
4" WCP
10" WCP
Maximum pressure
7" WCP
11" WCP
Contact local gas supplier if you are not sure about the inlet pressure.
Burner Input Requirements
Input ratings shown on the model/serial rating plate are for elevations up to 2,000 ft (609.6
m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a rate of 4% for each 1,000 ft
(304.8 m) above sea level (not applicable for Canada).
GAS SUPPLY PRESSURE TESTING
Gas supply pressure for testing regulator must be at least 1" (2.5 cm) water column pressure
above the manifold pressure shown on the model/serial rating plate.
Line pressure testing above 0.5 psi gauge (14" WCP)
The range and its individual shutoff valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of 0.5 psi (3.5
kPa).
Line pressure testing at 0.5 psi gauge (14" WCP) or lower
The range must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).