WARNING
Risk of injury or damage to the meter due to high
measured currents/measured voltages at the
connections of the current transformers!
High measurement currents can cause temperatures
of up to 80°C (176°F) on the connections of the
current transformers
· Use wiring that is designed for an operating
temperature of at least 80°C (176°F)!
· Only use current transformers with basic insu-
lation to IEC61010-1:2010!
· Make sure that screw terminals for the current
transformer connection on the device are ade-
quately tightened!
· Comply with the information and provisions in
the documentation of your current transform-
ers!
· Ground connections present on the secondary
windings of the current transformers must be
connected to ground!
· The current transformers can be hot even after
the power supply has been switched off. Allow
the connections of the current transformers
and the connecting cables to cool down before
touching them!
CAUTION
Risk of injury or damage to the basic device (mod-
ule) and/or your system due to a short circuit!
Inadequate insulation at the current measurement in-
puts of the modules with respect to the supply circuits
of the basic device can cause dangerous voltages
at the measurement input or damage to your device
(module)/system.
· Ensure reinforced or double insulation with
respect tothe supply circuits!