78
13.4 Decommissioning the system
Isolate the heat pump from power by switching the 3 pole
isolator switch to o.
Isolate the indoor unit from the mains by switching o and
removing the fuse, then remove the power cable from the fused
spur.
Recover the refrigerant into a cylinder specifically for this
purpose weighing and recording this using the appropriate
documentation.
Drain the heating circuit and remove all redundant pipework.
Disconnect and remove the refrigerant lines.
Disconnect the hydraulic connections.
Destroy or recycle the components in accordance with local or
national legislation.
Procedure:
1. Check the quantity of refrigerant present in the system. If extra
refrigerant has been added, this should be stated on the field
charge label on the outdoor unit. See §8.6.6 (point 7).
2. Ensure that no refrigerant is able to escape into the atmosphere.
3. Perform an analysis beforehand to see if the refrigerant can be
reused.
4. Isolate the power supply.
5. Weigh and record the weight of the recovery cylinder before
starting.
6. Connect manifold, gauges and recovery pump etc.
7. Keep the recycling cylinder on a scale.
Recovery cylinders should never be overfilled.
Keep an eye on the temperature as well as the operating
pressure: these cannot be exceeded.
8. Begin the recovery procedure.
9. Close the isolation / service valves on the device.
10. The cylinders should be removed from the location as soon as
possible.
IMPORTANT
Prior to recovering refrigerant:
Wear the correct PPE safety equipment.
Ensure there is 230V supply to the unit.
Have the correct tools at hand.
The devices or cylinders used to collect the
refrigerant must meet all applicable standards
and be completed to ISO 11650.
Decommissioning the system can only be performed by an F-gas
certified installer. Aer the system has been decommissioned, the
installer must apply a signed and dated label.
This label states that the system has been decommissioned and the
refrigerant has been removed, see GOV.UK for further guidance.
13.4.1 Removing and recycling
13.4.2 Collecting refrigerant
13.4.3 Label
Decommissioning can only be completd by an F-Gas qualified and
registered engineer.