76
13 MAINTENANCE
Check the water pressure in the system through the WiFi control
screen, or the boiler display where applicable.
Fill and vent the system if necessary.
The recommended water pressure is 1.5 to 2 bar.
If the system requires a top up twice a year or more, check
for leaks.
Isolate the indoor unit from the mains power by switching o
the fused spur and removing the fuse.
Loosen the screw below the indoor unit and remove the front
cover; see §8.3.3.
Ensure all pipework and refrigerant lines have cooled down.
Ensure that all sensors are correctly located and that the
wiring is not damaged or disconnected. Repair/replace if
necessary.
Ensure there are no water leaks, repair where required.
Replace the front cover and tighten the screw under the device;
see §8.3.3.
Clean the outside of the unit with a damp cloth. Do not use
aggressive or abrasive cleaning agents or solvents.
Re-establish the power supply by replacing the fuse and
switching on the fused spur.
Acquire a readout from the device using the Wi-Fi control screen.
13.2 Indoor unit maintenance work
CAUTION
When the system has just been operating,
certain components may be hot to touch.
Clean the filter. Proceed as follows:
1. Isolate the power to both the CH-boiler and the indoor units.
2. Close the boiler isolation valves and filter spigot valve.
3. Unscrew the system filter drain valve cap.
4. Use the drain valve cap to open the drain valve.
5. Unscrew and remove the magnet from the filter.
6. Drain the dirty water from the filter into a bucket or hosepipe by
slowly opening the spigot valve at the bottom of the filter.
7. Close the drain valve again.
8. Replace the magnet back into the filter.
9. Open the boiler and spigot isolation valves.
10. Check the system pressure and if necessary increase to 1.5 to bar.
11. Re-establish the power to both the CH-boiler and the indoor
units.
13.1 Cleaning the filter
The entire hybrid heat pump system must be serviced and cleaned on an annual basis by an authorised installer.
Srew cap
Ring collar
Magnet
Inlet/outlet port
Compression olive
Compression nut
Cap and key
Spigot valve
Filter Body
Drain valve
Drain valve rubber washer
Intergas recommend using our own
system filter as illustrated.
When using a dierent manufacturers
magnetic and hydronic separation filter
please refer to their instructions for
maintenace and cleaning.