Parameter Category Setting
Default
value Description/Setting range
P067P067
Connections
Function of digital output 2 relay
(Connector X4, contacts 1, 2 and 3)
0
0 = not in use
1 = signal, cooling active
2 = signal, heating active
3 = control of the secondary CH pump
4 = Hybrid boiler ON/OFF
5 = indoor unit on (P000 = 1)
6 = secondary pump (even during defrosting)
7 = locked status
8 = locked/notification status
9 = heat pump malfunction
10 = Sec. pump (active during heat pump and
boiler)
P068P068
Connections
Function of AUX 1 relay
(Connector X13, contacts 4 and 5)
0
0 = not in use
1 = signal, cooling active
2 = signal, heating active
3 = control of the secondary CH pump
4 = Hybrid boiler ON/OFF
5 = indoor unit on (P000 = 1)
6 = secondary pump (even during defrosting)
7 = locked status
8 = locked/notification status
9 = heat pump malfunction
10 = Sec. pump (active during heat pump and
boiler)
P069P069
Connections
Function of AUX 2 relay
(Connector X13, contacts 1 and 2)
0
0 = not in use
1 = signal, cooling active
2 = signal, heating active
3 = control of the secondary CH pump
4 = Hybrid boiler ON/OFF
5 = indoor unit on (P000 = 1)
6 = secondary pump (even during defrosting)
7 = locked status
8 = locked/notification status
9 = heat pump malfunction
10 = Sec. pump (active during heat pump and
boiler)
P081P081
System
Setting IDU pump output (maximum
pump control).
100 20 to 100%
P086P086
System
Minimum ∆T for heating. Reduces flow
rate when ∆T falls below set value.
0
0 = o (always uses the set flow rate)
1 to 15
P088P088
System (IDU) Pump mode 0
0 = standard pump control
1 = pump is operating continuously while in
stand-by
2 = pump is always operating (emergency
program)
P100P100
Bivalent
Setting hybrid/bivalent operation
mode
1
0 = entirely electric
1 = minimum COP (P101)
2 = ecological (based on CO emission)
3 = economical (based on rates)
4 = maximum heat pump use
5 = only the boiler (no heat pump)
P101P101
Bivalent
Setting minimum COP for heat pump
operation
2.0 1.0 to 10.0 (increments of 0.1)
P102P102
Bivalent
Setting the external temperature value
(Boiler will not be involved in heating
above this value).
15 ºC -20 ºC to 20 ºC (increments of 1 ºC).