Determine what device you want to control:
1) Only controls CO2 devices, such as a CO2 regulator or generator
(See section 3.4.1 Plant Mode without Fan);
2) Simultaneously controls CO2 device and ventilation fan (See
section 3.4.2 Plant Mode with Fan);
3) Only controls ventilation fans (See section 3.4.3 Human Mode).
3.4 Program the Parameters
06
Alarm high
value
9999ppm
(custom)
When CO2 ≥ 9999ppm,
it beeps.
50~9999
ppm
Alarm low
value
0
(custom)
When CO2 ≤ 0ppm,
it beeps.
0~9950
ppm
Professional
calibration
400ppm
(custom)
See 3.5.2
0~9900
ppm
3.3 Menu and Symbols
SV Display
Screen
Meaning
CO2 or Fan /
/
Plant mode without fan,
see 3.4.1
Plant mode with fan,
see 3.4.2
Human mode, see 3.4.3
CO2 Display
Screen
Function
Description
Range
CO2 on value
1200ppm
(custom)
When CO2 ≤ 1200ppm,
the CO2 outlet is on.
0~9950
ppm
CO2 off value
1600ppm
(custom)
When CO2 ≥ 1600ppm,
the CO2 outlet is off.
50~9999
ppm
Fan on value
2000ppm
(custom)
When CO2 ≥ 2000ppm,
the FAN outlet is on.
50~9999
ppm
Fan off value
1600ppm
(custom)
When CO2 ≤ 1600ppm,
the FAN outlet is off.
0~9950
ppm
Calibration
0
(custom)
See 3.5.1
-200~200
ppm
Alarm
The high/low level alarm
value to turn on the CO2 unit
The high/low level alarm
value to turn off the CO2 unit
(CF)
(CO2)
(AH)
(AL)
(PCAL)
(botH)
(FAN)
(ON)
(OFF)
(CoFF)
(Fon)
(FoFF)
(CAL)
(ALM)
(Con)