6 Function
6.1 Application area
The device
detects vibrations and the surface temperature of industrial machines (e.g. electric motors,
centrifugal pumps, fans, vertical bearings etc.) on non-rotating components.
provides condition indicators that enable the machine condition to be assessed in real time.
can be operated in SIO mode (standard input-output ) or in IO-Link mode.
The device provides many options for machine diagnostics.
Monitoring a machine unbalance
Detecting the actual machine uptime based on the vibration level
Detecting the switch-on operations of the machine
Accessing raw acceleration data for in-depth diagnostics
Bearing diagnostics using the demodulation method (BearingScout)
Device statuses can be visualised via a status LED on the device and signalled via IO-Link events.
6.2 IO-Link
IO-Link is a communication system for connecting intelligent sensors and actuators to automation
systems. IO-Link is regulated in the IEC 61131-9 standard.
General information about IO-Link can be found at io-link.ifm.
The Input Output Device Description (IODD) with all parameters, process data and detailed
descriptions of the device can be found at documentation.ifm.com.
IO-Link offers the following advantages:
Noise immune transmission of all data and process values
Parameter setting during operation or default setting outside the application
Parameters to identify the connected devices in the plant
Additional parameters and diagnostic functions
Automatic backup and restore of parameter sets in case of device replacement (data storage)
Logging of parameter sets, process values and events
Device description file (IODD – Input Output Device Description) for easy configuration
Standardised electrical connection
Remote maintenance
6.3 Switching function
The switching output OUx changes its switching status if it is above or below the set switching limits.
Hysteresis or window function can be selected.
VV devices offer the option of setting switching limits in all three measurement axes: