FOU2 Response of the analogue signal when a diagnostic case is signalled:
> Instead of the measured temperature value a defined current value according
to Namur NE43 is provided (On: 21�5 mA; OFF: 3�5 mA)
dOU1 Response of the diagnostic switching output when a diagnostic case is signalled:
> Output opens / closes / pulsates depending on the category of the diagnostic
case�
Setting options see Table 4 → 5.3.5
P-n Switching logic for the diagnostic switching output: pnp or npn�
HI Read max� value of the temperature measured in the process�
LO Read min� value of the temperature measured in the process�
Fnr Read fault number → 11 Fault correction
rES Restoring the factory settings�
It is recommended to note down your own settings before carrying out a
reset (→ 12 Factory setting)
9 Operation
When the supply voltage is applied, the unit is in the RUN mode after a power-on
delay time of 8 s (= normal operating mode)� It carries out its measurement and
evaluation functions and provides output signals according to the set parameters�
10 Technical data
Technical data and scale drawing at www�ifm�com�
10.1 Setting range for drW / drA
Medium temperature Setting range
-10���100 °C 14���212 °F 0�2���5 K
-25���0 °C -13���32 °F 0�3���5 K
> 100 °C > 212 °F x...5 K (→ chart)