► Connect the unit via the IO-Link interface to a PC or PLC with suitable
parameter setting software�
IO-Link interface for connection of the sensor to a PC → www.ifm.com.
8.1 Adjustable parameters
Uni Setting of the standard unit of measurement: °C or °F�
OU2 Configuration of the analogue signal: I = 4���20 mA or Ineg = 20���4 mA
ASP Analogue start point for measured temperature value
AEP Analogue end point for measured temperature value
drW Drift warning threshold: If this value of the temperature deviation is exceeded, a
diagnostic message of the category "warning" is provided with setting [drEd] =
OFF�
°C/°F = Maximum permitted temperature deviation of both sensor elements from
the mean value� Setting range → 10.1�
OFF = Drift warning deactivated�
drA Drift alarm threshold: If this value of the temperature deviation is exceeded, a
diagnostic message of the category "alarm" is provided with setting [drEd] =
ONdr or OFF�
°C/°F = Maximum permitted temperature deviation of both sensor elements from
the mean value� Setting range → 10.1�
OFF = Drift alarm deactivated�
drF Drift failure threshold: [drF] = drA + 3 K; if this value of the temperature deviation
is exceeded, a diagnostic message of the category "failure" is provided�
• drF cannot be set but results from the setting of drA�
• Setting drA = OFF automatically results in: drF = 8 K
ddr Delay of the drift detection�
ddr = Time span (0�5���300 min) for which a drift value must be above the
warning threshold drW or alarm threshold drA so that a diagnostic signal
is provided�
drEd Setting of the diagnostic cases (→ 5.3.3) for which diagnostic messages are
provided�
ON = Diagnostic cases of the category "failure" are signalled�
ONdr = Diagnostic cases of the categories "alarm" and "failure" are signalled�
OFF = Diagnostic cases of the categories "warning", "alarm" and "failure" are
signalled�