Ultrasonic flow meter without display SUHxxx
© ifm electronic gmbh 11661449 / 01 07 / 2025 31
10.3 Application configuration
The chapter describes the setting options for adaptation to your specific application.
10.3.1 Standard unit of measurement
It is possible to set a unit of measurement for each process value, on which further parameter settings will
be based.
Selectable values:
Flow uni.F:
SUHxx0: l/min; l/h; m
3
/h; m/s.
SUHxx1: l/min; l/h; m
3
/h; m/s; gal/min; gal/h; ft/s; oz/min.
Temperature uni.T:
SUHxx0: °C.
SUHxx1: °C; °F.
10.3.2 Process value for OUT1 and OUT2
The process value to be output via OUTx can be selected using the parameter SELx.
Selectable values:
FLOW: Flow
TEMP: Temperature
10.3.3 Damping
The set damping constant stabilises the output signals. Abrupt changes in the physical process values are
smoothed out.
This concerns the outputs and the process value transmission via the IO-Link interface.
The damping constant dAP is used to set after how many seconds the output signal reaches 63 % of the
final value if the measured value changes suddenly.
The damping constant is added to the response time of the sensor ( Technical data).
The UL and OL signals are defined under consideration of the damping time.
Measured value damping only has an effect on the process value flow.
10.3.4 Output polarity
The output polarity is set via the parameter P-n.
The setting affects both switching outputs.
PnP: The switching output is positive switching.
nPn: The switching output is negative switching.