Switch point Teaching
Change output function:
(normally open normally closed or normally closed normally open)
Error message:
If the setting was not successful
e.g. too short or too long teaching or
system pressure outside the measuring range
the signal at pin 2 is not supplied. The previous setting remains effec-
tive.
Installation and set-up / Operation
After mounting, wiring and setting check whether the unit operates
correctly.
22
2
*by local push-button, remote push-button or plc
**You can evaluate the signal by a PLC, you can also use this signal for a
signal lamp (Imax = 250mA).
Set the requested pressure and keep it constant.
Apply the operating voltage
(+U
B
) to pin 2 (min. >2s, max. <5s).*
After teaching the sensor supplies a
signal at pin 2 for 2s (= confirmation
of successfull setting).**
L-
L
+
>2 ... <5s 2s
Apply the operating voltage
(+U
B
) to pin 2 (min. >5s, max. 10s).*
After setting the sensor supplies a
signal at pin 2 for 2s (= confirmation
of successfull setting).**
L-
L
+
>5 ... 10s 2s