Factory default values
Installation
Before mounting and removing the sensor, make sure that no
pressure is applied to the system .
Screw the sensor into a G¼ process connection. Tightening torque
recommended 25Nm (max. 50Nm).
Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power before connecting the unit.
Wiring:
21
ENGLISH
2Sensor with Teach function (factory setting)
Switch point (SP)
25% of value of measuring range;
(is set to new value by Teach function)
Hysteresis 2% of value of measuring range
Switching function
1 Teach input
Delay time
Damping
normally open (normally closed selectable)
for setting to the desired pressure value (pin 2)
1 switching output semiconductor output, p-switching (pin 4)
0s
0.06s
L-
L
+
OUT
IN (Teach)
3
2
4
1
BU
BK
WH
BN
Core colours of ifm sockets:
1 = BN (brown),
2 = WH (white),
3 = BU (blue),
4 = BK (black).