IFM PP7534 handleiding

20 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 10 van 20
Set the following parameters:
hysteresis / width of the window (SP1, rP1)
OU2 = tch (pin 2 configured as teach input)
Switching function for output 1 (OU1)
Additionally you can set:
Delay time and damping for the switching outputs (dS1, dr1, dAP)
p-switching or n-switching (P-n)
When using the hysteresis function (Hno or Hnc) set the hysteresis
by the difference between SP1 and rP1.
During the teach operation the switch-on point is set to the current
system pressure (P
sys
). The hysteresis remains constant.
If the hysteresis is greater than allowed for the switch-on point
(switch-off point would be below the measuring range), the teach
operation is cancelled (the sensor provides an error signal, page
22). Reduce the difference between SP1 and rP1 and start the teach
operation again.
26
5 Freely configured sensor with Teach function
t
P
P
sys
1
0
1
0
SP
rP
HY
set the hysteresis teach operation
Hno
hysteresis
teach instant
Hnc
hysteresis function / N.O. (Hno)
hysteresis function / N.C. (Hnc)
window function / N.O. (Fno)
window function / N.C. (Fnc)

Bekijk gratis de handleiding van IFM PP7534, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelPP7534
CategorieNiet gecategoriseerd
TaalNederlands
Grootte1737 MB