IFM MFH219 handleiding
Handleiding
Je bekijkt pagina 19 van 29

Pressure-resistant position sensor for hydraulic cylinders MFH2xx
© ifm electronic gmbh 11660562 / 00 06 / 2025 19
Select Parameter > Teach.
Select Teach Select and set the switching output SSC1.x.
Save the changed parameter settings on the device.
Execute the command: Teach SP1.
Teach Result. State shows the status of the teach process.
The switch point SP1 is set for the selected switching channel.
Move the piston to the desired position for switch point 2.
Ensure that the current measured value is within the limits of the measuring range.
Execute the command: Teach SP2.
Teach Result. State shows the status of the teach process.
The switch point SP2 is set for the selected switching channel.
10.6.2 Window teach
In case of window teach Teach window, both switch points are taught for the selected switching channel
SSC1.x on the basis of the current piston position.
In the Window mode, the switch point SPx is set exactly to the current measured value:
• SP1 = current measured value – teach window size/2
• SP2 = current measured value + teach window size/2
The switch points for the window teach can also be set manually. Other window widths are
possible with manual configuration.
Parameter setting:
Install the device in the cylinder.
Select Parameter > SSC1.x.
Select SSC1.x Config.Mode and set the mode: Fenster.
Move the piston to the desired position for switch point 1.
Ensure that the current measured value is within the limits of the measuring range.
Select Parameter > Teach.
Select Teach Select and set the switching output SSC1.x.
Save the changed parameter settings on the device.
Execute the command: Teach Fenster.
Teach Result. State shows the status of the teach process.
The switch points SP1 and SP2 are set for the selected switching channel.
10.7 Diagnostics
The device provides the following diagnostic information via the IO-Link interface:
• Switching cycle monitoring
20
• Operating hours counter
21
• Switch-on operations
21
• Internal temperature
21
Diagnostic cases are: