Electronic sensor for level and temperature LT39xx
29
9.6.10 Configuration of the display
u Select [diS] and set type of indication:
• [On] = The display is switched on in the operating mode. (Update of the measured values 500 ms).
• [OFF] = The display is switched off in the operating mode. When one of the buttons is pressed, the
current measured value is displayed for 30 s.
The indicator LEDs remain active even if the display is deactivated.
[diS]
9.6.11 Resetting all parameters to factory setting
u Select [rES], then press [Set] and keep it pressed until [----] is displayed.
u Briefly press [Mode/Enter].
w The device reboots and then the factory settings are restored.
Note: on delivery the device is not operational. First, the basic settings must be entered.
[rES]
9.7 Setting values / setting ranges
9.7.1 Setting values [OFS]
[cm]
Setting range 0…200.0
LTx922 / LTx923 LTx924
Step increment 0.5 1
If values for [OFS] are entered, the "Setting ranges switching limits for level" and "Setting values
for [OP]" increase by this OFS value!
9.7.2 Setting ranges switching limits for level
The values in the table apply to [OFS] = [0].
If [OFS] > [0], they increase by the set OFS value.
LT3922 LT3923 LT3924
[cm] [cm] [cm]
[SP1] / [FH1] 2.5...20.0 3.5...39.0 6...59
[rP1] / [FL1] 2.0...19.5 3.0...38.5 5...58
Step increment 0.5 0.5 1
9.7.3 Setting ranges switching limits for temperature
[°C]
[SP1] / [FH1] -19.5...90
[rP1] / [FL1] -20...89.5
Step increment 0.5
9.7.4 Setting values for [OP]
The values in the table apply to [OFS] = [0].
If [OFS] > [0], they increase by the set OFS value.