LT39xx Electronic sensor for level and temperature
22
SP1
u Press [Mode/Enter] until the requested parameter is displayed.
2: Set parameter value
150
170
u Press [SET] and keep it pressed.
w Current setting value of the parameter flashes for 5 s.
w After 5s: The Setting value is changed.
Incrementally by pressing the button once or continuously by keeping the button pressed.
w The numerical values are incremented continuously:
For reducing the value:
u Let the display move to the maximum setting value. Then the cycle starts again at the minimum
setting value.
3: Acknowledge parameter value
SP1
u Briefly press [Mode/Enter].
w The parameter is displayed again. The new setting value is saved.
Setting of other parameters:
u Start again with step 1.
Finishing the parameter setting:
u Press [Mode/Enter] several times until the current measured value is displayed, or wait for 30 s.
w The sensor returns to the process value display.
If [C.Loc] is displayed when you try to change a parameter value, a parameter setting process is
active via the IO-Link communication (temporary locking).
If [S.Loc] is displayed, the sensor is permanently locked via software. This locking can only be
removed with a parameter setting software.
Change from menu level 1 to menu level 2: