Evaluation unit for monitoring and converting frequency signals DW3003
31
10 Troubleshooting
Display LED / process data bit Error Troubleshooting
[SC-1] Status: red (flashes at 1 Hz)
Output 1: yellow (flashes at 4 Hz)
Short circuit / overload at digital
output 1.
Remove short circuit / overload at digital
output OUT1.
[SC-2] Status: red (flashes at 1 Hz)
Output 2: yellow (flashes at 4 Hz)
Short circuit / overload at digital
output 2.
Remove short circuit / overload at digital
output OUT2.
[SC-3] Status: red (flashes at 1 Hz) Short circuit / overload at ana-
logue output (only for voltage
output).
Remove short circuit / overload at ana-
logue output OUT3.
[SC-SS] Status: red (flashes at 1 Hz) Short circuit / overload at sensor
supply.
Remove short circuit / overload at sen-
sor supply +.
[OL] Status: red (flashes at 1 Hz)
Input 1: off
Fault In1: high
Frequency at input 1 above
measuring range.
Signal at analogue output above
operating range.
Check input signal.
Check analogue output parameters.
[UL] Status: red (flashes at 1 Hz)
Input 1: off
Fault In1: high
Signal at analogue output below
operating range.
Check analogue output parameters.
[Warn] Status: red (flashes at 1 Hz) Load for analogue output too
high (only for current output).
Check load.
[PARA] Status: red (flashes at 1 Hz) Invalid parameter set. Check parameter settings.
[Err] Status: red (flashes at 1 Hz)
Output 1: off
Output 2: off
Device temperature too high. Reduce device temperature.
Status: red (flashes at 1 Hz)
Status: red Device faulty. Replace the device.
Status: off Supply voltage too low. Check/correct supply voltage.
Status: double flashing
Input 1: double flashing
Restart 1: double flashing
Reset 1/2: double flashing
: double flashing
Output 1: double flashing
Output 2: double flashing
Locator Start activated. Deactivate locator.
[Loc] Parameter setting via pushbut-
tons disabled.
Unlock pushbuttons:
Locking / unlocking (Ò/22)
[C.Loc] Parameter setting via pushbut-
tons locked due to active IO-Link
parameter setting.
Wait until parameter setting via IO-Link
is finished.
[S.Loc] Parameter setting via pushbut-
tons disabled by software.
Unlocking only possible via IO-Link in-
terface/IO-Link parameter setting soft-
ware.
LEDs or process data bits that are not listed can exhibit any behaviour.