Evaluation unit for monitoring and converting frequency signals DW3003
17
6.7.3 Analogue output (OUT3)
The analogue output provides an analogue signal that is proportional to the PDV in MDC1. (Parameter
setting: Output configuration (analogue / digital) (Ò/24) and Analogue output (Ò/25)).
Either a 4...20 mA or a 0...10 V signal can be output as an analogue signal. It is not possible to output
both signal types simultaneously.
The max. possible resistance of the connected load for the 4...20 mA current loop can only be
operated if the device is supplied via an AC voltage supply or a DC voltage supply of at least 24 V. If
the supply voltage falls below 24 V, the maximum resistance for the connected load is 300 ohm.