Remote I/O module 8DO 8DI AL4302
59
9.3.10 Using energy monitoring
The energy monitoring data is transmitted in the cyclic process data.
The measuring accuracy of the current and voltage values of the device supply US is ±10%.
When activating and configuring the submodule [Digital Output Energy Monitoring], IEC addresses are
automatically created for the following process data:
Supply voltage US error indication
Supply voltage UA error indication
Present voltage value of supply voltage US
Present current value of supply voltage US
Present voltage value of supply voltage UA
Present current value of supply voltage UA
Supply voltage US error indication
Supply voltage UA error indication - ports 1&2
Supply voltage UA error indication - ports 3&4
Present voltage value of supply voltage US
Present current value of supply voltage US
Present voltage value of supply voltage UA
Present current value of supply voltage UA - ports 1&2
Present current value of supply voltage UA - ports 3&4
Position of the energy monitoring data in the cyclical input data: Submodule: Digital Output Energy
Monitoring (Ò/78)
Requirements:
ü Device is integrated in PROFINET project.
ü The submodule [Digital Output Energy Monitoring] is activated and configured.
u Connect the IEC addresses of the subslots with symbols in the global variable list.
w The user can access the energy monitoring data via symbol names in the application.
9.3.11 Accessing data records acyclically
The user can access configuration and process data acyclically via data records.
The device supports the following data records:
Data record: Counter configuration (Ò/79)
Data record: main counter (Ò/80)
Data record: batch counter (Ò/81)
Note: Read data record
u Read the data record with the function block RDREC.
Specific parameters:
Input ID: HW_ID of the subslot (project-specific); properties of the
subslot
Input INDEX: index of the data record