IFM AL4302 handleiding

83 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 23 van 83
Remote I/O module 8DO 8DI AL4302
23
7 Operating and display elements
7.1 LEDs
2 3
4
5
11
1
4
5
6
6
8
88
8
6
6
7
7
9
99
9
7
7
10
1: Status: RDY
2: Status: BF
3: Status: SF
4: PROFINET: LNK
5: PROFINET: ACT
6: Process connection: DO1
7: Process connection: DO2
8: Process connection: DI1
9: Process connection: DI2
10: Voltage supply: UA
11: Voltage supply: US
7.1.1 Status
LED Description Colour State Description
RDY Gateway status - Off Not active or reboots
Green Flashes 3s (1Hz) DCP signalling service initiated via fieldbus
Flashes (5Hz) Error
Flashes (200ms on,
800ms off)
Firmware update running
On OK
Red On Error during firmware update (e.g. firmware not
compatible)
BF PROFINET connection sta-
tus (bus failure)
- Off No error
Red Flashes (2Hz) No data transmission
On No configuration or
physical connection with low speed or
no physical connection
SF System status (system fail-
ure)
- Off No error
Red Flashes 3s (1Hz) DCP signalling service initiated via fieldbus
On Watchdog expired or
channel diagnosis, general or extended
diagnosis available or
system error