IFM AL4203 handleiding
Handleiding
Je bekijkt pagina 23 van 82

Remote I/O module 8DO 8DI AL4203
23
7.1.2 Ethernet
LED Description Colour State Description
LNK Status of the connection - Off No Ethernet connection
Green On Ethernet connection established
ACT Status of the data transmis-
sion
- Off No data transmission
Yellow Flashes Data transmission
7.1.3 Process connections
LED Description Colour State Description
DO1 Signal level digital output
(pin 4)
- Off Digital output - pin 4: LOW
Yellow On Digital output - pin 4: HIGH
red flashes Error
• Short circuit after 24 V (if DO1 = LOW)
• Short circuit after GND / overvoltage (if DO1 =
HIGH)
On Output is not controlled by application
DO2 Signal level digital input (pin
2)
- Off Digital output– pin 2: LOW
Yellow On Digital output– pin 2: HIGH
Red Flashes Error
• Short circuit after 24 V (if DO2 = LOW)
• Short circuit after GND / overvoltage (if DO2 =
HIGH)
On Output is not controlled by application
DI1 Signal level digital input (pin
4)
- Off Digital input - pin 4: LOW
Yellow On Digital input - pin 4: HIGH
DI2 Signal level digital input (pin
2)
- Off Digital input - pin 2: LOW
Yellow On Digital input - pin 2: HIGH
7.1.4 Voltage supply
LED Description Colour State Description
US Power supply US status - Off No supply voltage is applied or the applied supply
voltage is too low (<4.5V)
Green On Supply voltage applied
Red On Overvoltage, undervoltage, short circuit at sensor
supply
UA Status power supply UA - Off No supply voltage is applied or the applied supply
voltage is too low (<6V)
Green On Supply voltage applied
Red On Undervoltage / overvoltage / short circuit at actua-
tor supply
Bekijk gratis de handleiding van IFM AL4203, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | AL4203 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 7189 MB |







