Remote I/O module 8DO 8DI AL4203
23
7.1.2 Ethernet
LED Description Colour State Description
LNK Status of the connection - Off No Ethernet connection
Green On Ethernet connection established
ACT Status of the data transmis-
sion
- Off No data transmission
Yellow Flashes Data transmission
7.1.3 Process connections
LED Description Colour State Description
DO1 Signal level digital output
(pin 4)
- Off Digital output - pin 4: LOW
Yellow On Digital output - pin 4: HIGH
red flashes Error
Short circuit after 24 V (if DO1 = LOW)
Short circuit after GND / overvoltage (if DO1 =
HIGH)
On Output is not controlled by application
DO2 Signal level digital input (pin
2)
- Off Digital output– pin 2: LOW
Yellow On Digital output– pin 2: HIGH
Red Flashes Error
Short circuit after 24 V (if DO2 = LOW)
Short circuit after GND / overvoltage (if DO2 =
HIGH)
On Output is not controlled by application
DI1 Signal level digital input (pin
4)
- Off Digital input - pin 4: LOW
Yellow On Digital input - pin 4: HIGH
DI2 Signal level digital input (pin
2)
- Off Digital input - pin 2: LOW
Yellow On Digital input - pin 2: HIGH
7.1.4 Voltage supply
LED Description Colour State Description
US Power supply US status - Off No supply voltage is applied or the applied supply
voltage is too low (<4.5V)
Green On Supply voltage applied
Red On Overvoltage, undervoltage, short circuit at sensor
supply
UA Status power supply UA - Off No supply voltage is applied or the applied supply
voltage is too low (<6V)
Green On Supply voltage applied
Red On Undervoltage / overvoltage / short circuit at actua-
tor supply