IFM AL4043 handleiding

59 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 23 van 59
Remote I/O module 16 DI AL4043
23
Name Description Value range Access
[connectiontimeout] Set timeout for interruption of
the fieldbus connection (value
in milliseconds)
20: 20 ms
30000: 30000ms (default)
60000: 60000 ms
rw
1
[byteswap] Order of the bytes in data
WORD
0: Big-Endian (default)
65535: Little-Endian
rw
1
1
Read and write
To set the ModbusTCP-specific parameters:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device is established (online).
u Select the [fieldbus] > [configuration] menu.
w The menu page shows the current settings.
u Setting ModbusTCP-specific parameters.
u Write the changed values to the device.
w ModbusTCP-specific parameters are set.
9.1.3.3 Reading the connection status
Available information:
Name Description Value range Access
[connectionstatus] Status of the ModbusTCP connection Disconnected: Not connected
Connected: Connected
ro
1
[disconnectioncounter] Connection interruption counter 0: no interruption
65535: 65535 interruptions
ro
1
[fieldbusfirmware] Firmware version of the ModbusTCP
stack
e.g. 5.4.0.3 (ModbusTCP Server) ro
1
1
Read only
Requirements:
ü The parameter setting software has been started.
ü The detailed view of the device is active.
u Select the [fieldbussetup] menu.
w The menu page displays the status of the ModbusTCP connection.
9.1.4 Process connections
The [io] menu provides access to the parameters of the process connections.
9.1.4.1 Configuring the input filters
u Observe the notes on input filters: Digital input filters (Ò/8)
Available parameters:

Bekijk gratis de handleiding van IFM AL4043, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.