IFM AL4042 handleiding

58 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 24 van 58
AL4042 Remote I/O module 16 DI
24
9.1.6 Ports: Configuring input filters
u Observe the notes on input filters: Digital input filters (Ò/8)
Available parameters:
Name Description Value range Access
[pin2]/[debounce_time] Pin 2: debounce time (= value *
0.1ms)
0: 0ms (default)
500: 50ms
rw
1
[pin2]/[hold_time] Pin 2: Hold time (= value * 0.1ms) 0: 0ms (default)
60000: 6000 ms
rw
1
[pin2]/[hold_level] Pin 2: Hold level 0: hold LOW
1: hold HIGH (default)
rw
1
[pin2]/[invert] Pin 2: Inversion 0: do not invert (default)
1: invert
rw
1
[pin4]/[debounce_time] Pin 4: debounce time (= value *
0.1ms)
0: 0 ms
500: 50ms
rw
1
[pin4]/[hold_time] Pin 4: Hold time (= value * 0.1ms) 0: 0ms (default)
60000: 6000 ms
rw
1
[pin4]/[hold_level] Pin 4: Hold level 0: hold LOW
1: hold HIGH (default)
rw
1
[pin4]/[invert] Pin 4: Inversion 0: do not invert (default)
1: invert
rw
1
1
The parameter can only be changed if no connection to the fieldbus controller is active
u Select the menu option [io] > [port[n]] (n: 1…8).
w The menu page displays the available parameters.
u Set the parameters.
u Write the changed parameter values to the device.
w The digital input filters have been configured.
9.1.7 Ports: Reading digital input data
Available information:
Name Description Value range Access
[pin2]/[digital] Process value digital input - pin 2 (af-
ter filtering)
LOW: Off
HIGH: On
ro
1
[pin4]/[digital] Process value digital input - pin 4 (af-
ter filtering)
LOW: Off
HIGH: On
ro
1
1
Read only
Requirements:
ü The parameter setting software has been started.
ü The detailed view of the device is active.
u Select the menu option [io] > [port[n]] (n: 1…8).
w The menu page displays the current process values of the port’s digital inputs.