IFM AL4042 handleiding
Handleiding
Je bekijkt pagina 24 van 58

AL4042 Remote I/O module 16 DI
24
9.1.6 Ports: Configuring input filters
u Observe the notes on input filters: Digital input filters (Ò/8)
Available parameters:
Name Description Value range Access
[pin2]/[debounce_time] Pin 2: debounce time (= value *
0.1ms)
• 0: 0ms (default)
…
• 500: 50ms
rw
1
[pin2]/[hold_time] Pin 2: Hold time (= value * 0.1ms) • 0: 0ms (default)
…
• 60000: 6000 ms
rw
1
[pin2]/[hold_level] Pin 2: Hold level • 0: hold LOW
• 1: hold HIGH (default)
rw
1
[pin2]/[invert] Pin 2: Inversion • 0: do not invert (default)
• 1: invert
rw
1
[pin4]/[debounce_time] Pin 4: debounce time (= value *
0.1ms)
• 0: 0 ms
…
• 500: 50ms
rw
1
[pin4]/[hold_time] Pin 4: Hold time (= value * 0.1ms) • 0: 0ms (default)
…
• 60000: 6000 ms
rw
1
[pin4]/[hold_level] Pin 4: Hold level • 0: hold LOW
• 1: hold HIGH (default)
rw
1
[pin4]/[invert] Pin 4: Inversion • 0: do not invert (default)
• 1: invert
rw
1
1
The parameter can only be changed if no connection to the fieldbus controller is active
u Select the menu option [io] > [port[n]] (n: 1…8).
w The menu page displays the available parameters.
u Set the parameters.
u Write the changed parameter values to the device.
w The digital input filters have been configured.
9.1.7 Ports: Reading digital input data
Available information:
Name Description Value range Access
[pin2]/[digital] Process value digital input - pin 2 (af-
ter filtering)
• LOW: Off
• HIGH: On
ro
1
[pin4]/[digital] Process value digital input - pin 4 (af-
ter filtering)
• LOW: Off
• HIGH: On
ro
1
1
Read only
Requirements:
ü The parameter setting software has been started.
ü The detailed view of the device is active.
u Select the menu option [io] > [port[n]] (n: 1…8).
w The menu page displays the current process values of the port’s digital inputs.
Bekijk gratis de handleiding van IFM AL4042, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | AL4042 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 4907 MB |







