AL4042 Remote I/O module 16 DI
22
9.1.3 Fieldbus: Configuring a ModbusTCP interface
Changes to the [byteswap] parameters will only take effect after the device has been restarted.
Available parameters:
Name Description Value range Access
[dhcp] Status of the DHCP client of the de-
vice
Static IP: IP parameters are set by the
user
DHCP: IP parameters are set by a
DHCP server in the network (default)
BOOTP: IP parameters are set via the
Bootstrap Protocol
rw
1
[ipaddress] IP address of the ModbusTCP inter-
face
e.g. 192.100.0.10
192.168.1.250 (default)
rw
1
[subnetmask] Subnet mask of the network segment e.g. 255.255.255.0
255.255.255.0 (default)
rw
1
[ipdefaultgateway] IP address of the network gateway e.g. 192.100.0.1
0.0.0.0 (default)
rw
1
[macaddress] MAC address of the Ethernet inter-
face
e.g. 00:02:01:0E:10:7F ro
2
[hostname] Name of the device in the Mod-
busTCP network
e.g. al4x4x ro
2
[connectiontimeout] Set timeout for interruption of the
fieldbus connection (value in millisec-
onds)
20: 20 ms
31000: 31000ms (default)
60000: 60000 ms
rw
1
[byteswap] Arrangement of the bytes in data
WORD
0: Big Endian (default)
65535: Little Endian
rw
1
1
Read and write
2
Read only
To configure the ModbusTCP interface:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
u Select the [fieldbussetup] > [network] menu.
w The menu page shows the current settings.
u Set IP parameters of the interface.
u Select [fieldbussetup] > [configuration] in the menu.
u Set fieldbus-specific parameters.
u Write the changed values to the device.
u Restart the device.
w The ModbusTCP interface is configured
9.1.4 Fieldbus: Reading the connection status