IFM AL4033 handleiding
Handleiding
Je bekijkt pagina 23 van 61

Remote I/O module 16 DI AL4033
23
9.1.3 Configuring the device
The [Parameter] menu page provides access to the configuration options of the device.
The parameters can only be changed if the device is in one of the following ECAT operating
modes: PRE-OPERATIONAL, SAFE-OPERATIONAL
Requirements:
ü IoT Core Visualizer has been started.
u Select the [Parameter] menu.
w The menu page shows the available parameters of the device.
9.1.3.1 Configuring input filters
u Observe the notes on input filters: Digital input filters (Ò/8)
Available parameters:
Name Description Value range Access
[pin2] > [debounce_time] Pin 2: debounce time (= value * 0.1milli-
seconds)
• 0: 0ms (default)
…
• 500: 50 ms
rw
1
[pin2] > [hold_time] Pin 2: hold time (= value * 0.1milliseconds) • 0: 0ms (default)
…
• 60000: 6000 ms
rw
1
[pin2] > [hold_level] Pin 2: hold level • Low: hold LOW
• High: hold HIGH (default)
rw
1
[pin2] > [invert] Pin 2: inversion • Signal not inverted: do not invert
(default)
• Signal inverted: invert
rw
1
[pin4] > [debounce_time] Pin 4: debounce time (= value * 0.1milli-
seconds)
• 0: 0ms (default)
…
• 500: 50 ms
rw
1