IO-Link input/output module AL2607
19
Parameter Index Subindex Value
Incre-
ments
Factory setting
SP1 SSC X1.0 Param (60)
SSC X1.1 Param (62)
SSC X1.2 Param (16384)
SSC X1.3 Param (16386)
SSC X1.4 Param (16388)
SSC X1.5 Param (16390)
SSC X1.6 Param (16392)
SSC X1.7 Param (16394)
1 -32000…32000 1 5000
SP2 2 -32000…32000 1 4000
Logic SSC X1.0 Config (61)
SSC X1.1 Config (63)
SSC X1.2 Config (16385)
SSC X1.3 Config (16387)
SSC X1.4 Config (16389)
SSC X1.5 Config (16391)
SSC X1.6 Config (16393)
SSC X1.7 Config (16395)
1 0 [High active]
1 [Low active]
- [High active]
Mode 2 0 [Deactivated]
1 [Single point]
2 [Window]
3 [Two Point]
- [Two point]
Hyst 3 0 - 3000 1 100
Tab.7: SSC X1.x Param and SSC X1.x Config
4.13.2 Function diagrams
The device provides digital switching signals via switching signal channels (SSC = Switching Signal
Channel).
The device has 8 digital switching signal channels, SSC1.0 to SSC1.7, which can be used to output
the process value.
Explanation of the numbering of the switching signal channels SSCx.y:
x = process value; y = switching signal channel
The switching signal channels can only be evaluated via the IO-Link interface.
The parameters for each switching signal channel can be set individually.
The switch point mode, switch points and the switch point logic are set when the switching signal
channel parameters are set.
Switch point mode
You can choose between the following switch point modes:
[Deactivated]
[Single Point Mode]
[Two Point Mode]
[Window Mode]
The switching signal channel changes to the active state depending on the process data value (PDV).
The active state is above the switch point in [Single Point Mode] and [Two Point Mode] and within the
window section in [Window Mode].
Switch point logic
By setting the switch point logic [High active] or [Low active], you can specify which value the
switching signal channel has in the active state:
[High active]: The switching signal channel is “high” in the active state (= ON = normally open = 1)
[Low active]: The switching signal channel is “low” in the active state (= OFF = normally closed = 0)
The following figures show the status of the switching signal channels depending on the switch point
mode, switch point logic and process data value (PDV).