IFM AL2507 handleiding
Handleiding
Je bekijkt pagina 8 van 27

AL2507 IO-Link input/output module
8
Parameter Index Subindex Value Increments Factory setting
Port Mode X1.0 15105 1 0 – 5, 7, 8 1 0
Port Mode X1.1 3 0 – 5, 7, 8
Port Mode X1.2 5 0 – 6, 8
Port Mode X1.3 7 0 – 6, 8
Port Mode X1.4 9 0 – 5, 8
Port Mode X1.5 11 0 – 5, 8
Port Mode X1.6 13 0 – 5, 8
Port Mode X1.7 15 0 – 5, 8
4.6 Voltage supply
4.6.1 Supply voltage US
The US supply voltage supplies the device and IO-Link with voltage.
4.6.2 Supply voltage UA
UA supplies the outputs of the ports X1.0...X1.7 with voltage.
4.6.3 Behaviour in case of undervoltage
If the voltage supply of the outputs (UA) falls below 16 V, all outputs switch off.
4.6.4 Limit values, protection against excessive current
AL2507
Total current 16 A
Power supply for sensors (pin1) 800 mA
Max. total current per port group 8 A
Max. current per port 2 A
The total current is limited to 16 A. Each individual port has a current limitation of 2A. If the current of
one port is too high, the device switches off the overloaded port until the current is within the
permissible range again.
4.6.5 Derating
Observe the derating of the current carrying capacity as a function of the ambient temperature as
follows:
Bekijk gratis de handleiding van IFM AL2507, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.