Parameter Index Subindex Value
Incre-
ments
Factory setting
Output COM lost / PD Invalid X1.6 - 1 15000 13 0 [OFF],
1 [ON],
2 [KEEP LAST]
1 0
Output COM lost / PD Invalid X1.6 - 2 14
Output COM lost / PD Invalid X1.7 - 1 15
Output COM lost / PD Invalid X1.7 - 2 16
Subindex access: true
In the [Acyclic Enhanced] operating mode, the following options are also possible for each output:
For the PWM output:
[OFF] = 0% duty cycle
[ON] = 100% duty cycle
[KEEP LAST] = last valid duty cycle
For the PWM-I output:
[OFF] = 0 mA (0% duty cycle)
[ON] = I
max
(PID control)
[KEEP LAST] = last valid requested current (PID control)
4.3 Electrical isolation of the voltage supply
The voltage supply of the ports (UA) is electrically isolated from the voltage supply of the IO-Link
master (US).
An electrical connection between US and UA eliminates the electrical isolation. This can lead to
increased interference in the IO-Link communication.
4.4 Parameter setting
IO Device Description (IODD) with all parameters and process data of the unit can be found at
documentation.ifm.com.
4.5 Inputs/ outputs
The device has 8 ports (X1.0...X1.7).
Each port has 2 inputs/outputs, which can operate in the following 9 modes:
Port mode Pin 2 Pin 4
0 (default) Digital input Digital input
1 Digital input/output Digital input/output
2 Analogue input (4...20 mA) Digital input/output
3* Analogue input (0...20 mA) Digital input/output
4 Analogue input (0...10 V) Digital input/output
5* Analogue input (0...5 V) Digital input/output
6* (only for ports X1.2 and X1.3) Digital input Frequency input 0…3 kHz
7* (only for ports X1.0 and X1.1) Digital input PWM
I
output 0...2000 mA
8* Digital input PWM output 0...1000‰
* only available in the [Acyclic Enhanced] operating mode