IFM AL2507 handleiding

27 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 11 van 27
IO-Link input/output module AL2507
11
Parameter Index Subindex Value (ms) Increments Factory setting
Input Debounce time X1.4 - 2 15100 10 0 – 50 1 0
Input Debounce time X1.5 - 1 11
Input Debounce time X1.5 - 2 12
Input Debounce time X1.6 - 1 13
Input Debounce time X1.6 - 2 14
Input Debounce time X1.7 - 1 15
Input Debounce time X1.7 - 2 16
Subindex access: true
4.7.2 Hold
This filter stretches short input pulses. The filter is configured via the following parameters:
Hold time: pulse duration to which short pulses are to be stretched. Pulses that are present for a
longer time than the hold time are not stretched.
Hold status: input level to be stretched (HIGH or LOW)
Time diagram hold filter with hold status HIGH:
t
1 1 1
2
Filter hold
output
IO-Link
process data
Filter hold
input
1: Hold time
2: Cycle time
Time diagram for hold filter with hold status LOW:
t
1 1 1
2
Filter hold
input
Filter hold
output
IO-Link
process data
1: Hold time
2: Cycle time
Input signals shorter than the cycle time are not reliably transmitted. To ensure a correct signal
transmission via IO-Link the hold filter must be used.
Parameter Index Subindex Value (ms) Increments Factory setting
Input hold time X1.0 - 1 15101 1 0 – 100 1 0
Input hold time X1.0 - 2 2
Input hold time X1.1 - 1 3
Input hold time X1.1 - 2 4