IFM AL1921 handleiding

135 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 43 van 135
IO-Link master with EtherNet/IP interface AL1921
43
deviceinfo/vendor/getdata
deviceinfo/productcode/getdata
Substructure: iotsetup
Available data points:
Name Description Value range Access
../security/securitymode Enabling / disabling security mode disabled: Security mode
deactivated
enabled: Security mode activated
rw
1
../security/password Password for authentication (Base64
coded)
wo
2
1
Read and write
2
write only
Valid character set for the Base64 coding / decoding of the password: UTF-8
Online tool for coding / decoding: www.base64encode.org
9.2.6.1 Example: Activating security mode
Task: The security mode of the IoT interface is to be activated. The valid password is to be set to
"password" (BASE64-coded: cGFzc3dvcmQ=).
Solution: Activating the security mode with data point iotsetup/security/securitymode . Writing
the password to the data point iotsetup/security/password .
Activating security mode
Request:
{
"code":"request",
"cid":1,
"adr":"/iotsetup/security/securitymode/setdata",
"data":{"newvalue":1}
}
Response:
{
"cid":-1,
"code":200
}
Setting the password
Request:
{
"code":"request",
"cid":2,
"adr":"/iotsetup/security/password/setdata",
"data":{"newvalue":"cGFzc3dvcmQ="}
}
Response:

Bekijk gratis de handleiding van IFM AL1921, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.