AL1921 IO-Link master with EtherNet/IP interface
42
If the access rights in the fieldbus projection software and the parameter setting software are set to
the [Fieldbus + IoT] value, the parameter values set on the fieldbus side always apply.
For exclusive access to the device via the parameter setting software, set the access rights to the
[IoT only] value and set the access rights to [Keep settings] in the fieldbus projection software.
If the access rights in the ifm IoT Core are set to the value [Fieldbus + IoT (read only)], the access
rights can no longer be changed via the ifm IoT Core. To regain write access with the parameter
setting software, set the access rights in the fieldbus projection software to the [Fieldbus + IoT]
value.
9.2.5 IoT: Configuring IP settings
Substructure: iotsetup/network
Available data points:
Parameter Description Value range Access
../dhcp Activate / deactivate DHCP mode static ip: DHCP client disabled; IP
parameters are set by the user
dhcp: DHCP client enabled; IP
parameters are set by the
network's DHCP server.
rw
1
../ipaddress IP address of the IoT interface e.g. 192.168.1.100
169.254.x.x (default)
rw
1
../subnetmask Subnet mask of the network segment e.g. 255.255.255.0
255.255.0.0 (default)
rw
1
../ipdefaultgateway IP address of the network gateway e.g. 192.169.1.1
0.0.0.0 (default)
rw
1
1
Read and write
Applicable services:
Name Description
../setblock write all data points of the substructure blockwise
Write the data points of the substructure only with the setblock service!
9.2.6 IoT: Configuring security mode
The unit provides a security mode. The security mode makes it possible to protect access to IO-Link
masters and connected IO-Link devices from the IT network. When security mode is activated, the
following restrictions apply:
Access only by authentication (password protection)
Access only via encrypted connection (TLS - Transport Layer Security)
The security mode only protects access and data transmission via the IoT interface.
w The user name administrator cannot be changed.
w The set password cannot be read with getdata.
The current status of the security mode can be read with the getidentity service (Ò Service:
getidentity/88).
For the authentication, the user must additionally provide the POST requests with a valid user name
and password in the field "auth". The user name and the password are shown as Base64-coded
character strings.
The following requests can be done if the security mode is enabled, also without authentication:
getidentity