IFM AL1591 handleiding

241 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 32 van 241
AL1591 SolutionBlock IO-Link master
32
Parameter Description Value range Access
[Network Mode] Method for the IP configuration of the
interface
Disabled: Schnittstelle deaktiviert
Static: DHCP client disabled IP parameters
are set by the user
DHCP: DHCP client enabled; IP parameters
are set by the network's DHCP server.
(Default)
link-local: IP settings are set automatically
(address range: 169.254.0.0 –
169.254.255.255, subnet mask: 255.255.0.0)
rw
1
[IP address] IP address of the IoT interface e.g. 192.168.1.100
169.254.x.x (default)
rw
2
[Subnet mask] Subnet mask of the Ethernet network e.g. 255.255.255.0
255.255.0.0 (default)
rw
2
[Default gateway IP ad-
dress]
IP address of the network gateway e.g. 192.169.1.1
0.0.0.0 (default)
rw
2
[Static DNS servers] Static DNS server e.g. 192.169.1.100 rw
2
[DNS servers] Active DNS servers e.g. 192.169.1.100 ro
3
[MAC address] MAC address of the IoT interface e.g. 00:02:01:05:66:C1 ro
3
[Hostname] Designation of the device in moneo
(diadram: ifm article number-serial
number)
ifm-AL1591-000242900024 ro
3
1
Read and write
2
Can only be changed if static addressing is active
3
Read only
To configure the IoT interface:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
u Select [IoT] menu.
w The menu page shows the current settings.
u Set the parameters.
u Write the changed values to the device.
w IP settings of the IoT interface are configured.
9.1.4 Fieldbus interface
The [Fieldbus] menu provides access to the parameters of the fieldbus interface.
9.1.4.1 Read status of the fieldbus connection
Available parameters:
Parameter Description Value range Access
[Fieldbus connection sta-
tus]
Status of the fieldbus connection Disconnected: interrupted
Connected: connected
ro
1
1
Read only
Requirements:
ü The parameter setting software has been started.
ü The connection to the device is established (online).

Bekijk gratis de handleiding van IFM AL1591, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelAL1591
CategorieNiet gecategoriseerd
TaalNederlands
Grootte20312 MB