AL1591 SolutionBlock IO-Link master
32
Parameter Description Value range Access
[Network Mode] Method for the IP configuration of the
interface
• Disabled: Schnittstelle deaktiviert
• Static: DHCP client disabled IP parameters
are set by the user
• DHCP: DHCP client enabled; IP parameters
are set by the network's DHCP server.
(Default)
• link-local: IP settings are set automatically
(address range: 169.254.0.0 –
169.254.255.255, subnet mask: 255.255.0.0)
rw
1
[IP address] IP address of the IoT interface e.g. 192.168.1.100
• 169.254.x.x (default)
rw
2
[Subnet mask] Subnet mask of the Ethernet network e.g. 255.255.255.0
• 255.255.0.0 (default)
rw
2
[Default gateway IP ad-
dress]
IP address of the network gateway e.g. 192.169.1.1
• 0.0.0.0 (default)
rw
2
[Static DNS servers] Static DNS server e.g. 192.169.1.100 rw
2
[DNS servers] Active DNS servers e.g. 192.169.1.100 ro
3
[MAC address] MAC address of the IoT interface e.g. 00:02:01:05:66:C1 ro
3
[Hostname] Designation of the device in moneo
(diadram: ifm article number-serial
number)
ifm-AL1591-000242900024 ro
3
1
Read and write
2
Can only be changed if static addressing is active
3
Read only
To configure the IoT interface:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
u Select [IoT] menu.
w The menu page shows the current settings.
u Set the parameters.
u Write the changed values to the device.
w IP settings of the IoT interface are configured.
9.1.4 Fieldbus interface
The [Fieldbus] menu provides access to the parameters of the fieldbus interface.
9.1.4.1 Read status of the fieldbus connection
Available parameters:
Parameter Description Value range Access
[Fieldbus connection sta-
tus]
Status of the fieldbus connection • Disconnected: interrupted
• Connected: connected
ro
1
1
Read only
Requirements:
ü The parameter setting software has been started.
ü The connection to the device is established (online).