IFM AL1590 handleiding
Handleiding
Je bekijkt pagina 28 van 241

AL1590 SolutionBlock IO-Link master
28
8 Set-up
8.1 Connect with IIoT network
The device is connected to the following instances via the IIoT interface:
• Parameter setting software, e.g. ifm moneo|configure
• Additional ifm IIoT devices at OT level, e.g. additional IO-Link masters
• IIoT applications, e.g. MQTT server or OPC UA clients
Behaviour of the IIoT interface during initial set-up:
• IP configuration via DHCP is active in the factory settings. The device is trying to obtain a valid IP
configuration from a DHCP server in the network.
• If no valid IP configuration can be obtained from a DHCP server, the IIoT interface is assigned an
IP address in the address range 169.254.0.0 to 169.254.255.255 using the link-local protocol.
u Connect the device to the IIoT network via port XI1, XI2.
u Call up the IoT Core Visualiser via the automatically assigned IP address.
u If necessary, set the IP configuration of the IIoT interface to manual addressing.
8.2 Connection to the fieldbus network
In the factory settings, the fieldbus interface has the following configuration:
Parameter PROFINET EtherNet/IP
IP address 0.0.0.0 192.168.1.250
Subnetwork 0.0.0.0 255.255.255.0
gateway 0.0.0.0 0.0.0.0
The IP configuration of the fieldbus interface can only be set via the respective fieldbus configuration
software.
ü The required fieldbus type is set.
u Connect the device to the fieldbus network via port XF1, XF2.
u Scan the network for devices in the fieldbus configuration software.
u Set the IP configuration of the fieldbus interface as required.
Bekijk gratis de handleiding van IFM AL1590, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | IFM |
Model | AL1590 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 20388 MB |