IFM AL1433 handleiding
Handleiding
Je bekijkt pagina 18 van 86

AL1433 IO-Link master with EtherCAT interface
18
7 Operating and display elements
7.1 LEDs
9
10
2 3
4
5
8
1
4
5
9
6
7
6
7
6
7
6
7
8
9
8
9
8
9
1: status: RDY
2: status: ERR
3: status: RUN
4: EtherCAT: LINK
5: EtherCAT: ACT
6:
IO-Link:
7: IO-Link: UA DO
8: IO-Link: DI
9: Power IN: UA
10: Power IN: US
7.1.1 Status
LED Description Colour State Description
RDY Gateway status Green Off Gateway: Not active or reboots
Flashes (5Hz) Gateway: Error
Flashes (200ms on,
800ms off)
Gateway: Firmware update running
On Gateway: OK
RUN EtherCAT status Green Off Device in “INIT” state
Flashes (2.5Hz) Device in “PRE-OPERATIONAL” state
Flashes (200ms on,
1000ms off)
Device in “SAFE-OPERATIONAL” state
Flashes (10Hz) Device starts and is not yet in the “INIT” state or
device is in the “BOOTSTRAP” state
On Device in “OPERATIONAL” state
ERR Error indication Red Off No error
Flashes (10Hz) Boot error
Flashes (200ms on,
200ms off, 200ms
on, 1000s off)
Watchdog error (EtherCAT or process data)
Flashes (200ms on,
1000ms off)
Local error
Flashes (2.5Hz) Invalid configuration
On Error in application controller
Bekijk gratis de handleiding van IFM AL1433, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | AL1433 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 7147 MB |