AL1431 IO-Link master with EtherCAT interface
44
w The menu page shows IO-Link events of the port.
9.2.4.7 Reading port events
A port event contains information about events on the IO-Link port (e.g. IO-Link device connected or
disconnected, change of the operating mode of the port).
Available parameters:
Name Description Value range Access
[portevent] Port event
Structure: 0x00ZZYY
0xYY: Device Status – status of the
IO-Link device
0xZZ: Connection Status – status of
the connection
DeviceStatus:
0x00: No IO-Link device connected
0x40: Wrong IO-Link device connected
0x80: IO-Link device connected and in
PREOPERATE state
0xFF: IO-Link device connected and in
OPERATE state
Connection Status:
0x00: Port disabled
0x01: Port activated, but no device
connected
0x02: Port activated and in "IO-Link"
operating mode
0x03: Port activated and in "DI" operating
mode
0x04: Port activated and in "DO" operating
mode
0x1B: Repetitions detected
0x1E: Short circuit detected at pin 4
0x42: Wrong revision of the IO-Link device
0x43: Wrong vendor ID (V1.1 revision)
0x44: Wrong device ID (V1.1 revision)
0x45: Wrong vendor ID (V1.0 revision)
0x46: Wrong device ID (V1.0 revision)
0x48: Wrong cycle time
ro
1
1
Read only
Requirements:
ü IoT Core Visualizer has been started.
ü The [Processdata] menu is active.
u Select the [Iolinkmaster] > [port[x]] submenu (x: 1…4).
w The menu page shows the port event of the port.