IO-Link master with EtherCAT interface AL1430
37
9.2.3.7 Restricting the current intensity of the supply voltages US/UA
The following electrical properties can be set for ports X1...X4:
Max. current intensity of the supply voltage US (pin 1 and pin 4)
Max. current intensity of the supply voltage UA (pin 2)
Available parameters:
Name Description Value range Access
[current_us_max] Max. current intensity of the supply
voltage US on the port (value in milli-
amps)
0: 0 mA
450: 450 mA (default)
2000: 2000 mA
rw
1
[current_ua_max] Max. current intensity of the supply
voltage UA on the port (value in milli-
amps)
0: 0 mA (default)
2000: 2000 mA
rw
1
1
Read and write
Requirements:
ü IoT Core Visualizer has been started.
ü The [Parameter] menu is active.
u Select the [Iolinkmaster] > [port[x]] > [powercontrol] submenu (x: 1…4).
u Set the parameters.
u Click on to save the changes to the device.
w The current intensities of the supply voltages have been restricted.
9.2.3.8 Configuring device validation and data storage
The device supports the functions device validation and backup / restore of parameter data of the
connected IO-Link devices.
The following options are available:
Option
Validation of the connected
IO-Link device
Backup of parameter values
Restore of parameter val-
ues
[No check and clear] No No No
[Type compatible V1.0 de-
vice]
Yes, test compatibility with IO-
Link standard V1.0
No No
[Type compatible V1.1 de-
vice]
Yes, test compatibility with IO-
Link standard V1.1
No No
[Type compatible V1.1 de-
vice with Backup + Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
Yes, automatic backup of pa-
rameter values; Changes to
the current parameter values
will be stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings
[Type compatible V1.1 de-
vice with Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
No, there is no automatic
backup; Changes to the pa-
rameter values are not stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings
Device validation and backup / restore of parameter values are only available if the “IO-Link”
operating mode of the port has been activated.
For options [Type compatible V1.1 device with Backup + Restore] and [Type compatible V1.1
device with Restore]: If the parameters [Vendor ID] or [Device ID] are changed in online mode,
the data memory is deleted and the parameter values of the connected IO-Link device are
backed-up again in the IO-Link master.
Available parameters: