AL1430 IO-Link master with EtherCAT interface
12
6 Electrical connection
6.1 Overview
FE
XF2XF1
XD1 XD2
X2X1
X4X3
FE: Functional earth (FE)
XF1: Ethernet port 1 (EtherCAT)
XF2: Ethernet port 2 (EtherCAT)
XD1: Power IN - voltage supply
XD2: Power OUT - voltage output
X1: IO-Link port (class B)
X2: IO-Link port (class B)
X3 IO-Link port (class B)
X4: IO-Link port (class B)
6.2 General wiring information
The unit must be connected by a qualified electrician.
u Observe the national and international regulations for the installation of electrical equipment.
The unit is only suitable for operation using SELV/PELV voltages.
u Take information about IO-Link configuration into consideration!
This device contains components that may be damaged or destroyed by electrostatic discharge
(ESD).
u Please observe the required precautions against electrostatic discharge!
By means of basic insulation according to EN61010-1, the circuits are isolated from each other and
from device surfaces that could be touched (secondary circuit with max. 30 V DC, supplied from mains
circuit up to 300 V overvoltage category II).
By means of basic insulation according to EN61010-1, the communication interfaces are separated
from each other and from device surfaces that could be touched (secondary circuit with V DC
maximum, supplied from mains circuit up to 300 V overvoltage category II). They are designed for
network environment 0 according to IEC TR62102).
6.2.1 Connection technology
The threaded connections in the device correspond to the M12 standard. To ensure compliance with
the specified protection rating, only cables that comply with this standard may be used. In the case of
self-assembled cables, the system manufacturer is responsible for the protection rating.
u Use connectors with gold-plated contacts.
u Check the screw connection 2 weeks after installation and retighten to the correct torque if
necessary.
u During installation, place the connectors vertically so that the coupling nut will not damage the
thread.
u Before connecting the connector, check that there is an undamaged O-ring in the socket.
u Observe the coding of the connectors during installation.
u Cover unused connections with protective covers. Tightening torque: 1.3 ± 0.1Nm