IFM AL1327 handleiding
Handleiding
Je bekijkt pagina 25 van 125

IO-Link master with EtherNet/IP interface AL1327
25
The set operating mode must match the operating mode of the device connected to the port (sensor,
actuator, IO-Link device).
Available parameters:
Parameter Description Value range Access
Mode Pin4 US Operating mode of Pin 4 (C/Q) of the
port
• Disabled: Port deactivated
• DI: Digital input
• DO: Digital output
• IO-Link: IO-Link process data
rw
1
1
Read and write
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
u Select the [Port x] (x = 1…8) menu.
w The menu page shows the current settings.
u Set the operating mode.
u Save the changes on the device.
w Operating mode of pin 4 (US) of the port has been set.
9.1.10 Ports: Setting the device validation and data storage
The device supports the functions device validation and backup / restore of parameter data of the
connected IO-Link devices.
The following options are available:
Option
Validation of the connected
IO-Link device
Backup of parameter values
Restore of parameter val-
ues
[No check and clear] No No No
[Type compatible V1.0 de-
vice]
Yes, test compatibility with IO-
Link standard V1.0
No No
[Type compatible V1.1 de-
vice]
Yes, test compatibility with IO-
Link standard V1.1
No No
[Type compatible V1.1 de-
vice with Backup + Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
Yes, automatic backup of pa-
rameter values; Changes to
the current parameter values
will be stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings
[Type compatible V1.1 de-
vice with Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
No, there is no automatic
backup; Changes to the pa-
rameter values are not stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings
Device validation and backup / restore of parameter values are only available if the “IO-Link”
operating mode of the port has been activated.
For options [Type compatible V1.1 device with Backup + Restore] and [Type compatible V1.1
device with Restore]: If the parameters [Vendor ID] or [Device ID] are changed in online mode,
the data memory is deleted and the parameter values of the connected IO-Link device are
backed-up again in the IO-Link master.
Available parameters: