IO-Link master with EtherNet/IP interface AL1325
49
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[2]/datastorage/getblobdata",
"data":{"pos":0,"length":h}
}
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[2]/datastorage/getblobdata",
"data":{"pos":h,"length":h}
}
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[2]/datastorage/getblobdata",
"data":{"pos":2*h,"length":h}
}
...
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[2]/datastorage/getblobdata",
"data":{"pos":n*h,"length":h}
}
Example:
1st reading order: pos = 0, length = 256
2nd reading order: pos = 256, length =256
3rd Read command: pos = 512, length = 256
Each segment is returned as a BASE64-encoded string.
u Connect segments (concatenate).
Restore data memory
u Determine the size of the backed-up data storage content (n = number of bytes).
Example: n = 550
u Read segment size (s = number of bytes)
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[1]/datastorage/chunksize/getdata"
}
Example: s = 256
u Start writing the data storage string segment by segment ("size" = size of the read data storage)
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[1]/datastorage/start_stream_set",
"data": {"size": n}
}
Example: size = 550